Leums Electric Corp. Foshan China
Main products:UPS,Inverter,Solar Charger
Products
Contact Us
  • Contact Person : Ms. feng feng
  • Company Name : Leums Electric Corp. Foshan China
  • Tel : 86-757-86112961
  • Fax : 86-757-82512690
  • Address : Guangdong,Foshan,2 Nanqi Street, Qinggong 3rd Road, Foshan City, Guangdong Province. China
  • Country/Region : China
  • Zip : 528000

ZX-T series Line-Interactive UPS

ZX-T series Line-Interactive UPS
Product Detailed
pure sine output,strong capacity of different load Smart RS232 communication port

Model ZX-T****

501L

102 M /102L

152 M /152L

202M/2020L

252M/252L

302M/302L

Rated capacity(VA/W)

500VA(300W)

1KVA(600W)

1.5KVA(900W)

2KVA(1200W)

2.5KVA(1500W)

3KVA(1800W)

 

 

Input

 

Commercial Power range(VAC)

100/110/120/127/220/230+25%,-35%

 

Output

AVR voltage rangeVAC

100/110/120/127/220/230±10%Auto-sensing

Transfer time

Typical5ms(Including detecdion time)

 

Battery

 

DC Voltage

12VDC

12/24VDC

24VDC

24/48VDC

 

Battery(standar model)

 

12V 7AH×2

12V

9AH×2

12V

12AH×2

12V 12AH×2/12V 9AH×4

12V 9AH×4

 

Appearsnce

 

External Size(mm)

D×W×H

375×130×190

452×192×338

Size(mm)

D×W×H

478×463×315(2piece)

584×335×495(1piece)

 

Net weight(kg)

6 .5

12(M)/10(L)

13(M)/11(L)

23(M)/17(L)

25(M)/20(L)

27.6(M)

/23.7(L)

 

Gross weight(kg)

15.6

26.6(M)/

22.6(L)

28.6(M)/

24.6(L)

25.8(M)/

19.8(L)

27.8(M)/

22.8(L)

30.4(M)/

26.8(L)

 

Input

FrequencyHz

60/50Hz±10%

Output

Waveform

sine-wave

Frequency

60/50Hz±0.5 Commercial power supply:shared frequency with the commercial inversion state: 60/50Hz±0.5

 

Protection

 

 

Overload

120%,10UPS; 150%,1UPS

UPS automatically shutdown if overload exceeds 120% of normal value for 10 seconds and 150% for 1 seconds

Short circuit

UPS

UPS output is cut off immediately or input circuit breaker protection

 

 

 

 

 

 

Battery

 

Type

Sealed, maintenance-free lead acid

Recharge current

(Long back up model):15A(Max.)

(standar moder):3A(Max.)

Backup time

((Long back up model):

(standar moder):(halfload)≥8(min)

Battery protection

,,

Automatic self-test ,discharge protecton over-charging protected,smart management system

 

ZX-T series Line-Interactive UPS